| Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC
 | 
| Operating voltage range | 85% to 110% of rated supply voltage | 
| Power consumption | Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
 | 
| Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II
 Platinum resistance thermometer: Pt100 or JPt100
 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
 Analog input
 Current input:4 to 20 mA or 0 to 20 mA
 Voltage input:1 to 5 V, 0 to 5 V, or 0 to 10 V
 | 
| Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB-N/THB-N.)
 | 
| Control method | ON/OFF control or 2-PID control (with auto-tuning) | 
| Control output
 | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) | 
| Voltage output (for driving SSR)
 | Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit | 
| Linear current output
 | 4 to 20 or 0 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000 | 
| Auxiliaryoutput
 | Number of outputs
 | 2 | 
| Output specifications
 | SPST-NO relay outputs: 250 VAC, E5CD: 3 A (resistive load), E5CD-B: 2 A (resistive load) Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference values)
 | 
| Event input
 | Number of inputs
 | 2 | 
| External contact
 input
 specifications
 | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | 
| Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | 
| Current flow: Approx. 7 mA per contact | 
| Transfer Output
 | Number of outputs
 | 1 (depends on model): Transfer output type | 
| Output specifications
 | Current output: 4 to 20 mA DC, Load: 500 Ω, Resolution: Approx. 10,000 Linear voltage output: 1 to 5 V DC, Load: 1 kΩ min., Resolution: Approx. 10,000
 | 
| Setting method | Digital setting using front panel keys | 
| Indication method | 11-segment digital display, individual indicators, and bar display Character height: PV: 14.9 mm, SV: 7.1 mm
 | 
| Multi SP * | Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications. | 
| Bank switching | None | 
| Other functions | Adaptive control, automatic filter adjustment, water-cooling output adjustment, indication data (power ON time monitor, ambient temperature monitor, and control output ON/OFF count monitors), parameter masking, operation after power ON, manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting | 
| Ambient operating temperature | -10 to 55°C (with no condensation or icing), For 3-year warranty: -10 to 50°C with standard mounting (with no condensation or icing) | 
| Ambient operating humidity | 25% to 85% | 
| Storage temperature | -25 to 65°C (with no condensation or icing) | 
| Altitude | 2,000 m max. | 
| Recommended fuse | T2A, 250 VAC, time-lag, low-breaking capacity | 
| Installation environment | Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1) |