| Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC
 | 
| Operating voltage range | 85% to 110% of rated supply voltage | 
| Power consumption | Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC
 All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W
 max. at 24 VDC
 | 
| Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II
 Platinum resistance thermometer: Pt100 or JPt100
 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to
 260°C
 Analog input
 Current input: 4 to 20 mA or 0 to 20 mA
 Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to
 the E5CC-U only for those manufactured in May 2014 or later.)
 | 
| Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB-N/THB-N.)
 | 
| Control method | ON/OFF control or 2-PID control (with auto-tuning) | 
| Control output
 | Relay output | E5CC/E5CC-B: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum
 applicable load: 5 V, 10 mA (reference value)
 E5CC-U:
 SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum
 applicable load: 5 V, 10 mA (reference value)
 | 
| Voltage output (for driving SSR)
 | Output voltage: 12 VDC ± 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
 | 
| Linear current output
 | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | 
| Auxiliaryoutput
 | Number of outputs
 | E5CC: 3 E5CC-B: 2
 E5CC-U: 1 or 2 (depends on model)
 | 
| Output specifications
 | SPST-NO relay outputs, 250 VAC, Models with 1 output: 3 A (resistive load), E5CC-U models with 2
 outputs: 3 A (resistive load), E5CC-B models with 2 outputs: 2 A (resistive load), Models
 with 3
 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load:
 10 mA at 5 V (reference value)
 | 
| Event input *1
 | Number of inputs | E5CC: 2 or 4 (depends on model) E5CC-B: 2 (depends on model)
 | 
| External contact input
 specifications
 | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | 
| Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | 
| Current flow: Approx. 7 mA per contact | 
| Transfer output *1
 | Number of outputs
 | 1 (only on models with a transfer output) | 
| Output specifications
 | Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000
 | 
| Setting method | Digital setting using front panel keys | 
| Remote SP input *1 *2 | Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.) Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)
 | 
| Indication method | 11-segment digital display and individual indicators Character height: PV: 15.2 mm, SV: 7.1 mm
 | 
| Multi SP *3 | Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or serial communications.
 | 
| Bank switching | None | 
| Other functions | Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100%
 AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop,
 protection functions, extraction of square root, MV change rate limit, logic operations,
 temperature status display, simple programming, moving average of input value, and
 display brightness setting
 | 
| Ambient operating temperature
 | -10 to 55°C (with no condensation or icing), For 3-year warranty: -10 to 50°C with standard mounting (with no condensation or icing)
 | 
| Ambient operating humidity | 25% to 85% | 
| Storage temperature | -25 to 65°C (with no condensation or icing) | 
| Altitude | 2,000 m max. | 
| Recommended fuse | T2A, 250 VAC, time-lag, low-breaking capacity | 
| Installation environment | Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1) |