| Pipe | 
| Fluid condition | Gas | 
| Applicable pipe diameter | Nominal diameter 50mm~5000mm (*1) | 
| Spool piece | Pipe diameter | 50mm~500mm (*2) | 
| Flange | JIS10k standard (*3) | 
| Material | SGP、SUS304  --- (*4) | 
| Socket | Standard type | Screw type Flange type (Screw  type with sensor)
 Flange type (Large  senor type)
 | 
| Sensor | 
| Installation requirement | Upper stream side 15D,Lower stream side 5D or more (D is inner diameter) | 
| Sensor probe | Gas・・・Standard (screw type) | nominal diameter 50mm~500mm(*5) temperature -30℃~180 ℃
 pressure -0.05Pa~1MPa  (-0.5 ~10kgf/cm )
 | 
| Large(flange type) | nominal diameter 500mm~(*5) temperature -30℃~180 ℃
 pressure -0.05Pa~1MPa  (-0.5 ~10kgf/cm )
 | 
| Seal | Probe fittings | Combine with gas seal unit | 
| Gas seal unit | standard, large, custom | 
| Gas seal adaptor | instead of gas seal unit (not used) | 
| Cable | Distance from sensor probe to converter, 6m or 10m (standard) | 
| Converter | 
| General | Measurement method | Ultrasonic transit time method | 
| Chordal path | 1 path or 2 path (option) | 
| Traverse | Z or V | 
| Measurement compensation range | temperature +/-25℃, pressure +/- 30% | 
| Accuracy | ± 1.0% FS (flow velocity 5 ~ 60m/s) | 
| Reproducibility | ±0.2% | 
| Flow velocity resolution | less than 0.5mm/s | 
| Averaging | Default 10 sec (0 ~ 180 sec variable) | 
| Ultrasonic thermometer | Measure temperature (in case of air) by ultrasound transit time | 
| Ambient temperature | -10~+50℃ | 
| Power supply | Power supply | AC100V±10%, 50/60Hz, AC115V, 220V (option) | 
| Surge protection | Built-in surge absorber | 
| Power dissipation | Max.25(W) | 
| Output | Analog output1 | Various flow output,DC4~20mA, isolatedOver range: DC0~24mA                                             Load resistance: Less than 1000Ω
 | 
| Analog output2 | Various flow output,reverse flow, temperature, pressure Range: DC4~20mA,isolated Over range: DC0~24mA Load resistance: Less than 1000Ω  | 
| Pulse output1 | Integrated pulseOpen collector standard 30V, 0.2A
 Pulse width: 1.6ms or 50ms
 | 
| Pulse output2 | AIntegrate pulse, alarm, normal and reverse flow, upper l and lower limitOpen collector standard 30V, 0.2A
 | 
| Pulse output3 | Alarm, normal and reverse flow, upper l and lower limitOpen collector standard 30V, 0.2A
 | 
| Pulse output4 | Alarm, normal and reverse flow, upper l and lower limitOpen collector standard 30V, 0.25A
 | 
| Power supply for pressure and temperature | DC24V+/-0.5V  0.2A | 
| Digital output | RS422×1  RS232C×1 | 
| Input | temperature | DC4~20mA | 
| Pressure | DC4~20mA | 
| Display | LCD | 128 x 240 dots LED back right | 
| Character | Alphanumeric, mathematical symbol (ex, +, -, Σ) | 
| Display contents | Measurement displayInstantaneous flow rate (analog1,2)、
 Integrated count (analog1,2)
 Max flow rate (analog1,2)、
 Input temperature, pressure,
 ultrasonic temperature meter
 It can display content of 4  in all contents.
 | 
| Configuration view | diameter, temperature, pressure, flow range | 
| Adjustment view | zero point adjusting, change of time constant, low-cut |