| Power rating | 30 W | 60W | 
| Rated output voltage (DC) | 5 V | 12 V | 24 V | 
| Indication monitor | None | None | None | 
| Efficiency * | 115 VAC input | 78% typ. | 85% typ. | 85% typ. | 
| 230 VAC input | 77% typ. | 86% typ. | 86% typ. | 
| Input conditions
 | Voltage range * | Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second)
 | 
| Frequency * | 50/60 Hz (47 to 450 Hz) | 
| Input current * | 115 VAC input | 0.53 A typ. | 0.99 A typ. | 1.1 A typ. | 
| 230 VAC input | 0.32 A typ. | 0.61 A typ. | 0.67 A typ. | 
| Power factor * | --- | 
| Leakage current *
 | 115 VAC input | 0.5 mA max. | 
| 230 VAC input | 1 mA max. | 
| Inrush current *
 | 115 VAC input | 16 A typ. | 
| 230 VAC input | 32 A typ. | 
| Output characteristics
 | Rated output current | 5 A | 4.5 A | 2.5 A | 
| Rated output power | 25 W | 54 W | 60 W | 
| Maximum boost current | 6 A | 5.4 A | 3 A | 
| Voltage adjustment range * | 4.5 to 5.8V (with V. ADJ) | 10.8 to 14 V (with V. ADJ) | 21.6 to 28 V (with V. ADJ) | 
| Ripple noise voltage *
 | 100 to 240 VAC input
 | 130 mVp-p max. at 20 MHz of bandwidth
 | 120 mVp-p max. at 20 MHz of bandwidth
 | 110 mVp-p max. at 20 MHz of bandwidth
 | 
| Input variation influence * | 0.5% max. | 
| Load variation influence * | 1.5% max. | 
| Temperature variation
 influence
 | 100 to 240 VAC input
 | 0.05%/°C max. | 
| Start up time * | 115 VAC input | 1000 ms max. | 1000 ms max. | 1000 ms max. | 
| 230 VAC input | 1000 ms max. | 1000 ms max. | 1000 ms max. | 
| Hold time * | 115 VAC input | 45 ms typ. | 20 ms typ. | 20 ms typ. | 
| 230 VAC input | 240 ms typ. | 120 ms typ. | 110 ms typ. | 
| Additional functions
 | Overload protection | Yes, automatic reset, intermittent operation type, Refer to Overload Protection on catalog for details.
 | 
| Overvoltage protection | Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again),
 Refer to Overvoltage Protection on catalog for details.
 | 
| Series operation | Yes (For up to two Power Supplies; external diodes required.) | 
| Parallel operation | Yes (For up to two Power Supplies), Refer to Parallel Operation on catalog for details.
 | 
| Output indicator | Yes (LED: Green) | 
| Alarm indicator | Yes (LED: Red) | 
| Indication monitor
 | Measurement and display
 details
 | Refer to Communication and Indication Items on catalog for details. | 
| Main display | None | 
| Ethernet communication
 | Measurement and display
 details
 | Refer to Communication and Indication Items on catalog for details. | 
| Communicationprotocol
 | EtherNet/IP, Modbus TCP | 
| Physical layer | 100BASE-TX | 
| Communicationspecifications
 | Refer to Communication Specifications on catalog for details. | 
| Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports), current cutoff 20 mA
 | 
| 2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA
 | 
| 1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA
 | 
| 0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA
 | 
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC
 | 
| 100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC
 | 
| Environment | Ambient operating temperature * | -40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing)
 | 
| Storage temperature | -40 to 85°C (with no condensation or icing) | 
| Ambient operating humidity | 95% max. (Storage humidity: 95% max.) | 
| Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions
 | 
| Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | 
| Reliability | MTBF * | 160,000 hrs typ. | 
| Life expectancy * | 10 years min. | 
| Construction | Weight | 250 g max. | 250 g max. | 250 g max. | 
| Cooling fan | No | 
| Degree of protection | IP20 by EN/IEC 60529 | 
| Power rating | 90 W | 120 W | 
| Rated output voltage (DC) | 24 V | 24 V | 
| Indication monitor | Included | None | Included | None | 
| Efficiency * | 115 VAC input | 86% typ. | 87% typ. | 90% typ. | 90% typ. | 
| 230 VAC input | 87% typ. | 88% typ. | 92% typ. | 92% typ. | 
| Input conditions
 | Voltage range * | Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second)
 | 
| Frequency * | 50/60 Hz (47 to 450 Hz) | 50/60 Hz (47 to 63 Hz) | 
| Input current * | 115 VAC input | 1.7 A typ. | 1.7 A typ. | 1.2 A typ. | 1.2 A typ. | 
| 230 VAC input | 1.0 A typ. | 1.0 A typ. | 0.63 A typ. | 0.63 A typ. | 
| Power factor * | --- | 0.9 min. | 
| Leakage current *
 | 115 VAC input | 0.5 mA max. | 
| 230 VAC input | 1 mA max. | 
| Inrush current *
 | 115 VAC input | 16 A typ. | 
| 230 VAC input | 32 A typ. | 
| Output characteristics
 | Rated output current | 3.75 A | 5 A | 
| Rated output power | 90 W | 120 W | 
| Maximum boost current | --- | 6 A | 
| Voltage adjustment range * | 23.0 to 24.1 V | 21.6 to 28 V (with V. ADJ) | 
| Ripple noise voltage *
 | 100 to 240 VAC input
 | 300 mVp-p max. at 20 MHz of bandwidth
 | 150 mVp-p max. at 20 MHz of bandwidth
 | 
| Input variation influence * | 0.5% max. | 
| Load variation influence * | 1.5% max. | 
| Temperature variation
 influence
 | 100 to 240 VAC input
 | 0.05%/°C max. | 
| Start up time * | 115 VAC input | 1000 ms max. | 1000 ms max. | 
| 230 VAC input | 1000 ms max. | 1000 ms max. | 
| Hold time * | 115 VAC input | 25 ms typ. | 35 ms typ. | 
| 230 VAC input | 130 ms typ. | 35 ms typ. | 
| Additional functions
 | Overload protection | Yes, automatic reset, intermittent operation type, Refer to Overload Protection on catalog for details.
 | 
| Overvoltage protection | Yes, 110% or higher of rated output voltage (90 W), 130% or higher of rated output voltage (120 W), power shut off
 (shut off the input voltage and turn on the input again,
 Refer to Overvoltage Protection on catalog for details.
 | 
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) | 
| Parallel operation | Yes (For up to two Power Supplies), Refer to Parallel Operation on catalog for details.
 | 
| Output indicator | Yes (LED: Green) | 
| Alarm indicator | Yes (LED: Red) | 
| Indication monitor
 | Measurement and display
 details
 | Refer to Communication and Indication Items on catalog for details.
 | 
| Main display | 7-segment LED (White)
 | None | 7-segment LED (White)
 | None | 
| Ethernet communication
 | Measurement and display
 details
 | Refer to Communication and Indication Items on catalog for details.
 | 
| Communicationprotocol
 | EtherNet/IP, Modbus TCP | 
| Physical layer | 100BASE-TX | 
| Communicationspecifications
 | Refer to Communication Specifications on catalog for details. | 
| Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports), current cutoff 20 mA
 | 
| 2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA
 | 
| 1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA
 | 
| 0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA
 | 
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC
 | 
| 100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC
 | 
| Environment | Ambient operating temperature * | -40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing)
 | 
| Storage temperature | -40 to 85°C (with no condensation or icing) | 
| Ambient operating humidity | 95% max. (Storage humidity: 95% max.) | 
| Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions
 | 
| Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | 
| Reliability | MTBF * | 110,000 hrs typ.
 | 150,000 hrs typ.
 | 110,000 hrs typ.
 | 140,000 hrs typ.
 | 
| Life expectancy * | 10 years min. | 
| Construction | Weight | 350 g max. | 400 g max. | 
| Cooling fan | No | 
| Degree of protection | IP20 by EN/IEC 60529 |