| Power ratings | 60 W | 120 W | 240 W | 480 W | 
| Output voltage (VDC) | 24 V | 24 V | 24 V | 24 V | 
| Efficiency (Typical) | 230 VAC input | 0.88 | 0.88 | 0.87 | 0.91 | 
| Input | Voltage *1 | 100 to 240 VAC, 90 to 350 VDC (allowable range: 85 to 264 VAC) *6 | 
| Frequency *1 | 50/60 Hz (47 to 450 Hz) | 50/60 Hz (47 to 63 Hz) | 
| Current (Typical)
 | 115 VAC input | 1.0 A | 2.2 A | 2.5 A | 4.8 A | 
| 230 VAC input | 0.7 A | 1.4 A | 1.3 A | 2.4 A | 
| Power factor
 (Typical)
 *7
 | 230 VAC input | 0.44 | 0.45 | 0.92 | 0.97 | 
| Harmonic current emissions | --- | Conforms to EN61000-3-2 | 
| Leakage current
 (Typical)
 | 115 VAC input | 0.19 mA | 0.19 mA | 0.24 mA | 0.26 mA | 
| 230 VAC input | 0.34 mA | 0.36 mA | 0.54 mA | 0.65 mA | 
| Inrush current
 (Typical)
 *2
 | 115 VAC input | 16 A | 
| 230 VAC input | 32 A | 
| Output | Voltage adjustment range *3
 | -10% to 15% (with V.ADJ) (guaranteed) | 
| Ripple at 20 MHz
 (Typical)
 *4
 | 230 VAC input | 70 mV | 120 mV | 150 mV | 130 mV | 
| Input variation influence | 0.5% max. (at 85 to 264 VAC input, 100% load) | 
| Load variation Influence (Rated Input voltage)
 | 1.5% max., at 0% to 100% load | 
| Temperature variation influence
 | 0.05%/°C max. | 
| Start up time
 (Typical)
 *2
 | 115 VAC input | 530 ms | 800 ms | 790 ms | 770 ms | 
| 230 VAC input | 410 ms | 760 ms | 750 ms | 670 ms | 
| Hold time (Typical)
 *2
 | 115 VAC input | 24 ms | 27 ms | 34 ms | 21 ms | 
| 230 VAC input | 117 ms | 128 ms | 36 ms | 22 ms | 
| Additionalfunctions
 | Overload protection *2 | 105% to 160% of rated load current | 
| Overvoltage protection *2 | Yes *5 | 
| Parallel operation | No | 
| Series operation | Possible for up to two Power Supplies (with external diode) | 
| Others | Ambient operating temperature
 | -25 to 60°C (Refer to Engineering Data) | 
| Storage temperature | -25 to 65°C | 
| Ambient operating humidity | 20% to 90% (Storage humidity: 10% to 95%) | 
| Dielectric strength (detection current: 20 mA)
 | 3.0 kVAC for 1 min. (between all inputs and outputs) 2.0 kVAC for 1 min. (between all inputs and PE terminal)
 1.0 kVAC for 1 min. (between all outputs and PE terminal)
 | 
| Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC | 
| Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
 | 
| 10 to 150 Hz, 0.35-mm single amplitude (5 G max for 60W, 120W, 240 W, 3 G max for 480 W) for 80 min. each in X, Y, and Z directions
 | 
| Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions | 
| Output indicatior | Yes (color: green), lighting from 80% to 90% or more of rated voltage | 
| EMI | Conducted Emission
 | Conforms to EN61204-3 EN55011 Class A and based on FCC Class A | 
| Radiated Emission
 | Conforms to EN61204-3 EN55011 Class A | 
| EMS | Conforms to EN61204-3 high severity levels | 
| Safety standards | UL Listed: UL508 (Listing) UL UR: UL No. 62368-1 (Recognition)
 cUL: CSA C22.2 No.107.1
 cUR: CSA C22.2 No.62368-1
 EN: EN 62477-1, EN 62368-1
 BIS: IS 13252 (Part1)
 | 
| Fulfilled Standards | SELV (EN 62368-1/EN 62477-1/UL No. 62368-1) | 
| Degree of protection | IP20 by EN/IEC60529 | 
| SEMI | F47-0706 (200 to 240 VAC) | 
| Weight | 260 g | 580 g | 940 g | 1,550 g |