| Item | Specifications | 
| Operationpower
 supply
 | Power supply voltage and frequency
 | K7DD-PQMA: 100 to 240 V AC, 50/60 Hz K7DD-PQMD: 24 V DC
 | 
| Operating power supply voltage range
 | 85% to 110% of the rated voltage | 
| Operating frequency range
 | 45 to 65 Hz | 
| Power consumption | K7DD-PQMA: 15.7 VA max. (100 to 240 V AC) | 
| K7DD-PQMD: 5.2 W max. (24 V DC) | 
| Recommend external fuse
 | T2A, time delay, high-breaking capacity | 
| Ambient operating temperature | -10 to 55°C | 
| Ambient operating humidity | 25% to 85% | 
| Storage temperature | -20 to 65°C (with no condensation or icing) | 
| Altitude | 2,000 m max. | 
| Insulation resistance | 20 mΩ min. Between the power supply terminals and the other terminals;
 Between all the terminals and the case;
 Between (communications terminals + trigger input terminals + alarm output
 terminals) and the other terminals;
 Between (voltage input terminals + CT input terminals) and the other terminals
 | 
| Dielectric strength | 2,000 V AC for 1 minute Between the power supply terminals and the other terminals;
 Between all the terminals and the case;
 Between (communications terminals + trigger input terminals + alarm output
 terminals) and the other terminals;
 Between (voltage input terminals + CT input terminals) and the other terminals
 | 
| Vibration resistance | Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s², 10 sweeps of 5 min each in X, Y, and Z directions
 | 
| Shock resistance | 100 m/s2, 3 times each in X, Y, and Z axes, 6 directions | 
| Degree of protection | IP20 | 
| Terminal block type | Push-In Plus | 
| Exterior color | Black (Munsell N 1.5) | 
| Mounting | DIN Track | 
| Weight | Approx. 360 g | 
| Wiring material
 | Wire type | Solid or Stranded wire | 
| Wiring material | Copper | 
| Recommended wires | 0.25 to 1.5 mm2 AWG 24 to AWG 16
 | 
| Stripping length (without ferrules)
 | 8 mm *, 10 mm, 12 mm * without ferrules | 
| Installation environment | Operation voltage: EN/IEC 61010-1 Pollution Degree 2, Overvoltage category II | 
| Measurement circuit: EN/IEC 61010-2-030 Pollution Degree 2, CAT II 600 V or CAT III 300 V
 | 
| Industrial electromagnetic environment
 | EN/IEC 61326-1 Industrial electromagnetic environment | 
| Safety standards | UL61010-1, Korean Radio Waves Act (KS C 9610-6-2, KS C 9811), RCM, UKCA |